Overview
P2S was contracted to provide engineering services for the renovation of Mayer Hall, a five story, 112,000 sq.ft, physics building and a new five story, 80,000 sq. ft, addition on the University of California, San Diego campus. This was performed in two phases with the addition being constructed first. Post renovation the building houses undergraduate physics teaching labs, physics research labs and faculty office space.
Challenge
The existing building utilized a central utility core that allowed for 12-foot floor-to-floor heights. The addition floor heights were matched to the existing building, but due to constrained site space the addition could not have a central utility core. Providing the required mechanical, electrical, plumbing and laboratory services in this limited height while maintaining sufficient clear space for research equipment represented the major challenge.
In addition, some of the utility systems that required modifications to increase capacity were located in the existing building. The challenge was to maintain service to existing building occupants while upgrading the systems in time for the addition to be occupied.
Action
Mayer Hall Addition
Variable air volume control for both the supply and exhaust systems was utilized in the building. Two variable air volume air-handling units supply air-conditioning to the building. Both units serve a combination of laboratory and office spaces. Three laboratory exhaust fans on a common intake plenum provide laboratory exhaust. All equipment was located on the roof. This configuration was designed to allow:
- All horizontal distribution of duct mains occurs on the roof. Three strategically located areas for vertical duct shafts were utilized to arrange supply, return and exhaust risers so that duct mains would not have to cross once the ducts left the shafts. This was done to accommodate the short floor-to-floor height.
- Improved diversity in equipment sizing by serving both space types from a common air handler.
- High efficiency lighting and day lighting control systems reduced heat gain from these systems. Occupancy sensors were utilized in non-laboratory spaces to further reduce the cooling load when unoccupied.
- Fume hood sash stops were set at 18” to reduce laboratory exhaust requirements.
- Duct routing was kept as direct as possible given the space constraints, low pressure drop fittings were used and mains were sized at 1,500 fpm to minimize fan static requirements.
- Velocities at cooling coils and filter banks were limited to 400 fpm to reduce static losses.
- All air handler and laboratory exhaust fans were provided with variable frequency drives. The manifolded exhaust fans are staged and fan speeds are adjusted to maintain a minimum 3,000 fpm discharge stack velocity.
- Since physics labs are not hood intensive, standard variable air volume boxes were utilized in both the laboratory supply and exhaust systems as a cost saving measure. The few hoods in the building were provided with constant volume lab control valves.
Other systems provided include: lab compressed air, lab waste, domestic hot/cold water, low flow plumbing fixtures, complete DDC control system and chilled water from campus central system.
Mayer Hall Renovation
- The existing pressure dependent variable air volume system was converted to a pressure independent operation through the addition of retrofit VAV boxes at each zone and in the lab exhaust.
- The high temperature hot water to heating hot water heat exchanger and pumping system were upgraded. The new system serves the addition as well as the existing building.
- A new electronics cooling water system was provided to serve lab equipment. The system utilizes campus chilled water and a plate and frame heat exchanger. A complete distribution system was provided to serve both the existing building and addition.
- The laboratory compressed air equipment was upgraded and interconnected with the compressed air system in two adjacent buildings to provide redundancy.
- High efficiency lighting and day lighting control systems were provided.
- Occupancy sensors were utilized in non-laboratory spaces to further reduce the cooling load when unoccupied.
Results
Completed project allowed UCSD to consolidate their physics teaching spaces providing undergraduates with new labs and easy access to professors and research labs. The layout of the building’s energy efficient systems was fully coordinated to meet the laboratory space needs within the short floor-to-floor height.